In This Article we are going to see SIEMENS BACnet Commercial Thermostat RDY2000BN Model Parameter List 101 to 911.
Sequence of Operation
Parameter | Definition | Default |
P101 | System Type | CO |
P102 | Cooling Stages | 2 |
P103 | Heating Stages | 2 |
P104 | Aux Heating Stages | 0 |
P105 | Fan Operation | ELE |
P106 | Reversing Value | 0 |
P107 | Scheduler Days | 2 |
P109 | Units | F |
P110 | Changeover | YES |
P111 | Changeover Deadband | 5°F (2.5 °C) |
P112 | Daylight Savings | NO |
P113 | Display Temp Setpoint | 0 = Absolute |
Parameter 201 to 225
Parameter | Definition | Default |
P201 | Heat Temp Limit | 95°F (35.0 °C) |
P202 | Cool Temp Limit | 50°F (10.0 °C) |
P203 | Temperature Display Offset | 0°F (0 °C) |
P204 | Override Time Limit | 2 |
P205 | Override Temp Limit | - |
P206 | Heat Pump Compressor Lock Out | OFF |
P207 | Heat Pump Auxiliary Heat Lockout | OFF |
P208 | Service UV Lamp | 0 |
P209 | Service Humidifier | 0 |
P210 | Service Air Filter | 0 |
P211 | Keypad Lockout | OFF |
P212 | Clock Format | 12 |
P213 | Backlight | 15 |
P214 | Humidity Display Offset | 0 |
P220 | Heating Setpoint Comfort | 70 |
P221 | Cooling Setpoint Comfort | 75 |
P222 | Heating Setpoint Economy | 62 |
P223 | Cooling Setpoint Economy | 82 |
P224 | Heating Setpoint Protection | 40 |
P225 | Cooling Setpoint Protection | 104 |
Parameter 301 to 320
Parameter | Definition | Default
|
P301 | Configurable Input 1 (IN 1) | OFF |
P302 | Temperature Input 1 Type | 1 |
P303 | Temperature Input 1 Low | 0°F (-18.0 °C) |
P304 | Temperature Input 1 High | 120°F (50 °C) |
P305 | Configurable Input 2 (IN 2) | OFF |
P306 | Temperature Input 2 Type | 1 |
P307 | Temperature Input 2 Low | 0°F (-18.0 °C) |
P308 | Temperature Input 2 High | 120°F (50 °C) |
P309 | Configurable Input 3 (IN 3) | OFF |
P310 | Temperature Input 3 Type | 1 |
P311 | Temperature Input 3 Low | 0°F (-18.0 °C) |
P312 | Temperature Input 3 High | 120°F (50 °C) |
P313 | Configurable Input 4 (IN 4) | OFF |
P314 | Temperature Input 4 Type | 1 |
P315 | Temperature Input 4 Low | 0°F (-18.0 °C) |
P316 | Temperature Input 4 High | 120°F (50 °C) |
P317 | Aux Output 1 (OUT 1) | OFF |
P318 | Aux Output 2 (OUT 2) | OFF |
P319 | Aux Output 3 (OUT 3 & C3) | OFF |
P320 | Independent Humidity Control | NO |
Parameter 401 to 407
Parameter | Definition | Default
|
P401 | Unit Number | - |
P402 | CO2 Setpoint | 1000 |
P403 | Pre-Occupancy Purge | OFF |
P404 | Occupancy Sensor Min Run Timer | 30 |
P405 | Semi-Continuous Fan | ON |
P407 | Installer Password | Current PW |
Parameter 501 to 511
Parameter | Definition | Default
|
P501 | Interstage Delay Cooling | 5 |
P502 | Interstage Differential Cooling | 1°F (0.5 °C) |
P503 | Cooling Minimum Off Time | 5 |
P504 | Cooling Minimum On Time | 3 |
P505 | Changeover Delay | 10 |
P506 | Cooling Deadband | 1°F |
P507 | Interstage Delay Heating | 5 |
P508 | Interstage Differential Heating | Conv = 1°F (0.5°C) HP = 2°F (1°C) |
P509 | Heating Minimum Off Time | 5 |
P510 | Heating Minimum On Time | 3 (10 if heat pump) |
P511 | Heating Deadband | 1°F (0.5 °C) |
Parameter 601 to 606 & 701,911
Parameter | Definition | Default
|
P601 | MS/TP MAC address | 255 |
P602 | Baud Rate | A = Auto |
P603 | Device Instance | 4194303 |
P604 | Max Master | 127 |
P605 | Serial number | Display only |
P606 | Max info frames | 1 |
| ||
P701 | Firmware | Display only |
| ||
P911 | Expert Password | Current PW |